Key Installation Notes for Pump Damping Pedestals

In industrial production and urban water supply systems, water pumps operate at high frequency, generating significant vibration and noise. Installing vibration isolators and damping pedestals is one of the most common and effective vibration isolation solutions. The following points should be noted during installation:

  1. Installation Sequence
    Reserve space for the anti vibration mounts on the waterproof foundation first, place the damping pedestal, install the shock isolators, and then position the pump on the isolation pedestal.

  2. Accurate Hole Alignment
    Ensure precise alignment of the upper and lower mounting holes of the vibration dampers to prevent twisting and loss of vibration isolation performance.

  3. Balanced Load Distribution
    Keep the pump's center of gravity as centered as possible. Avoid uneven loading and adjust the vibration isolator height to ensure proper leveling.

  4. Flexible Grounding Connection
    Use flexible copper wire for grounding to avoid creating rigid connections between the pedestal and the foundation.

  5. Do Not Embed Vibration isolators
    Vibration isolators must remain exposed and must not be covered or embedded in concrete.

  6. Proper Pedestal and Isolator Selection
    Design the pedestal and select vibration dampers according to the size of the waterproof foundation. Ensure bolt holes are positioned at least 100 mm away from the foundation edge.

  7. Avoid Load Concentration During Installation
    Begin installation from the side with more vibration dampers to prevent excessive load on only one or two isolators.

台座1

台座

Anlijing Vibration Reduction Technology Co., Ltd. specializes in the research, development, and manufacturing of vibration isolation products for a wide range of electromechanical equipment. The company offers five major product categories, including spring isolators, rubber isolators, air-film vibration isolators, air-cushion vibration isolators, and wire rope isolators, with thousands of models and specifications to meet diverse application requirements across the electromechanical industry.

In addition to standard products, Anlijing provides comprehensive vibration control services such as on-site vibration measurement, isolation system design, and customized product development, delivering reliable and effective vibration reduction solutions tailored to specific operating conditions.

Related technical information

Recommend product

Model selection

I don't know how to solve the low-frequency vibration problem of the equipment. Please contact the vibration reduction engineer at sale@anlijing.com

Customized

Customize vibration reduction products according to customer needs